武汉市雷创技术发展有限公司
DVACSP3P100SFM一体式电源防雷器,德国DEHN电源防雷器原装产品交货快---技术参数
Type Part No. |
DVA CSP 3P 100 S FM 900 367 |
德国盾DEHN防雷器DVACSP100S,一级电源防雷器,100KA电源防雷器
SPD according to EN 61643-11 / ... IEC 61643-11 type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 5m) type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN) 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [L-N] (UC) 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 μs) [L+N-PE] (Itotal) 100 kA |
Lightning impulse current (10/350 μs) [L-N]/[N-PE] (Iimp) 25 / 100 kA |
Nominal discharge current (8/20 μs) (In) 25 / 100 kA |
Voltage protection level [L-N]/[N-PE] (UP) ≤ 1.5 kV / ≤ 1.5 kV kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi) 25 kArms / 100 Arms |
Follow current limitation/Selectivity no tripping of a 35 gL/gG fuse up to 25 kArms (prosp.) |
Response time (tA) ≤ 100 ns |
Max. backup fuse (L) up to IK > 25 kArms 250 A gG |
由于防雷产品规格型号参数众多,更有同一型号下参数不同的产品,因此本链接的图片,价格,产品属性,仅供参考、不作交易价格、具体价格请在线咨询或以电话报价/书面报价为准 欢迎来电咨询!
DVACSP3P100SFM一体式电源防雷器,德国DEHN电源防雷器原装产品交货快---产品图片
防雷器事项
安装在民用及功能性建筑中的设备和系统出现故障是人们不愿看到的,并且代价非常大。因此,必须确保设备在正常操作期间和雷暴天期间能够无故障运行。在德国,每年记录在册的雷电活动数量,在多年来一直保持在一个高水平。根据保险公司提供的损伤数据显示,在雷电和电涌的防护方面,个人及商业机构均有明显的保护缺陷(图1)。
一个专业的解决方案涵盖了足够的保护措施。防雷区的概念,促使设计师,结构师以及运营人员在安装时考虑采取不同的保护措施。使得所有的相关设备及系统均能受到可靠合理的防护。